Motor FLA & Protection Calculator (NEC Art. 430)

Size conductors, breakers, and overload protection for safe motor operation.

1Motor Specs

Assumptions

  • Motor Type: Induction / Squirrel Cage
  • Wire Type: Copper, THHN (75°C Terminations)
  • Duty: Continuous
  • Protection: 250% of Table FLC

Full Load Current (FLC)

-Amps
NEC 430.248

Breaker

Short Circuit Protection

40 Amps

Max 250% of FLC (NEC 430.52). Rounded up to next standard size.

Wire Size

Branch Circuit

14 AWG

Min 125% of FLC (20.0A). Based on 75°C column.

NEMA Starter

Motor Controller

Size 0

Standard NEMA size for 1 HP @ 115V.

Overload

Heater Setting

18.4 Amps

115% of Table FLC.

Popular motor control Configurations

Motor Sizing Formula

Ibranch = 1.25 × Total FLC
Ioverload = Inameplate × Service Factor

NEC Article 430

Article 430 covers motors. Table 430.248 (1-phase) and 430.250 (3-phase) provide FLC currents. 430.52 dictates maximum short-circuit and ground-fault protection settings.

Frequently Asked Questions

Do I use nameplate amps or NEC table amps?

For sizing conductors and short-circuit protection (breakers/fuses), you MUST use NEC Table values. For sizing Overload protection (heaters), you use the Nameplate current.

What size breaker do I need for a motor?

Inverse time breakers are typically allowed up to 250% of the motor's FLC per Table 430.52 to handle inrush current without nuisance tripping.

What size wire do I need for a motor?

Conductors supplying a single motor must have an ampacity of at least 125% of the motor's FLC Rating (NEC 430.22).