CH 9
TABLE 4

PVC Schedule 80 Fill

NEC 2020 • 2023 • 2026 COMPLIANT

Capacity limits for heavy-wall Schedule 80 PVC (accounts for reduced internal area).

Trade SizeID (in)100% Area (in²)1 Wire (53%)2 Wires (31%)Over 2 (40%)60% Nipple
1/20.4650.1700.0900.0530.0680.102
3/40.6150.2970.1570.0920.1190.178
10.7940.4950.2620.1530.1980.297
1-1/41.0420.8520.4520.2640.3410.511
1-1/21.2201.1680.6190.3620.4670.701
21.5581.9051.0100.5910.7621.143
2-1/22.0493.2981.7481.0221.3191.979
32.5214.9942.6471.5481.9982.996
3-1/22.9156.6733.5372.0692.6694.004
43.3078.5884.5522.6623.4355.153
54.81318.1949.6435.6407.27810.916
65.76126.06713.8168.08110.42715.640

Professional Usage Disclaimer

This data is provided for informational purposes only. Always verify with the latest edition of the National Electrical Code (NFPA 70) and consult with a licensed electrical professional or AHJ (Authority Having Jurisdiction) before performing any electrical work. Zing² is a reference tool, not a substitute for qualified engineering.