CH 9
TABLE 8

Conductor Properties

NEC 2020 • 2023 • 2026 COMPLIANT

Resistance and reactance values for voltage drop math and stranded conductor areas.

Size (AWG/kcmil)Area (Circ. Mils)Diameter (in) [Class B]Copper Res (Ohms/kFT)Alum Res (Ohms/kFT)
144,1100.0733.075.04
126,5300.0921.933.17
1010,3800.1161.211.99
816,5100.1460.7781.28
626,2400.1840.4910.808
441,7400.2320.3080.508
266,3600.2920.1940.319
1/0105,6000.3720.1220.201
2/0133,1000.4180.09670.159
3/0167,8000.4700.07660.126
4/0211,6000.5280.06080.100
250250,0000.6410.05150.0847
300300,0000.6950.04350.0715
350350,0000.7440.03780.0620
400400,0000.7890.03360.0551
500500,0000.8930.02760.0453
600600,0000.9640.02230.0366
700700,0000.9860.01890.0310
750750,0000.9980.01760.0289
800800,0001.0290.01660.0272
900900,0001.0900.01470.0241
10001,000,0001.1520.01320.0216
12501,250,0001.2890.01060.0174
15001,500,0001.4120.008830.0145
17501,750,0001.5260.007560.0124
20002,000,0001.6320.006620.0108

Professional Usage Disclaimer

This data is provided for informational purposes only. Always verify with the latest edition of the National Electrical Code (NFPA 70) and consult with a licensed electrical professional or AHJ (Authority Having Jurisdiction) before performing any electrical work. Zing² is a reference tool, not a substitute for qualified engineering.