NEC 2026 Load Calc with an EV Charger

Properly size a new electrical service for a house or building.

Quick Answer

The NEC 2026 optional method adds an EV charger at 100% of its nameplate (120.82(D)), instead of putting it in the part counted at 40%. For this 2,400 sq ft home with a 48 A charger (11,520 VA), a range, dryer, water heater, dishwasher and 5 kVA of A/C, that is 34,120 VA (142.2 A), so a 150 A service.

142.2 A
150 A service · 34,120 VA · NEC 2026

142.2 A
34,120 VA
Optional Method · NEC 2026
System Voltage240 V
Gen. Lighting & App. Demand4,800 VA
Fixed Appliance Demand10,200 VA
Range Demand12,000 VA
Dryer Demand5,000 VA
EV Charger Demand11,520 VA
HVAC Demand5,000 VA

Recommendation

Based on the calculated load of 142.2 A:

Minimum Service Size150 A

Code, method and service

NEC edition

Article 120: 2 VA per sq ft. The optional method takes the first 8 kVA at 100% and adds an EV charger at 100%.

Method

NEC 220.82 (120.82 in 2026). Only for a service of 100 A or more; often gives a smaller service.

Service voltage

House

Outside dimensions; leave out open porches and garages

At least 2 for the kitchen and dining area (NEC 210.11(C)(1))

Usually 1 (NEC 210.11(C)(2))

Major appliances

Nameplate kW × 1,000. 0 for gas or none

Nameplate rating. 0 for gas or none

Nameplate volts × amps: a 48 A charger at 240 V is 11,520 VA. Not known? Use 7,200. 0 for none

Cooling or heat pump: volts × amps from the nameplate

Furnace, baseboard or strip heat

Heat type

Optional method counts 65%

Heating and cooling don't run at the same time, so only the larger one counts (NEC 120.60). NEC 2026 adds the EV charger at 100% (120.82(D)).

Fixed appliances

Appliances fastened in place, like a water heater, dishwasher or disposal. Leave out the range, dryer, EV charger, heating and A/C: they have their own boxes.

  • Water heater4,500 VA
  • Dishwasher1,200 VA

2 appliances, 5,700 VA at nameplate (NEC 120.82(B)).

Worked example: 2,400 sq ft, optional method, NEC 2026

A 2,400 sq ft home with these loads comes to 34,120 VA, which is 142.2 A at 240 V. The smallest listed service that covers it is 150 A.

  1. General lighting: 2,400 sq ft × 2 VA = 4,800 VA (NEC 2026 120.41). Receptacles in the living area are included in this figure.
  2. Small-appliance and laundry circuits: 2 × 1,500 VA + 1 × 1,500 VA = 4,500 VA (120.52(A) and (B)).
  3. Appliances at nameplate: 2 fixed appliances 5,700 VA, range 12,000 VA, dryer 5,000 VA. Total general load 32,000 VA (120.82(B)).
  4. Demand: the first 8,000 VA at 100% and the rest at 40% = 17,600 VA (120.82(B)).
  5. Heating and cooling, the larger of: cooling 5,000 VA at 100%, or heat 0 VA × 65% = 0 VA (120.82(C)(4)). Counted: 5,000 VA.
  6. EV charger at 100% of its nameplate: 11,520 VA (120.82(D) and 120.57).
  7. Service current: 34,120 VA ÷ 240 V = 142.2 A, so 150 A.

The optional method (120.82) is only for a dwelling served at 100 A or more. Adding a load to an existing home has its own method in 120.83. NEC 2026 moved these rules from Article 220 to Article 120. Check with the utility and the local inspector before picking the service size.

Understanding load calculation

A load calculation adds up what a home could draw at once, using the demand factors in NEC Article 220 (Article 120 in NEC 2026), to size the service entrance and feeders. The answer is in volt-amperes (VA); dividing by the service voltage gives amps.

What changed in NEC 2026: general lighting is 2 VA per sq ft instead of 3 (120.41). The optional method takes the first 8 kVA at 100% instead of 10 kVA (120.82(B)), and adds an EV charger at 100% of its nameplate (120.82(D)). The demand factors, the range and dryer rules and the heating shares stay the same. Pick the edition your area has adopted at the top of the calculator.

Which method should I use?

  • Standard (Article 220 Part III, or Article 120 Part III in NEC 2026) is allowed for any dwelling. It applies a demand factor to general lighting and receptacles, then adds the range, dryer, fixed appliances, EV charger and the larger of heating or cooling.
  • Optional (220.82, or 120.82 in NEC 2026) is only for a dwelling served at 100 A or more. It takes everything at nameplate, counts the first 10 kVA (8 kVA in NEC 2026) at 100% and the rest at 40%. It often gives a smaller service for a house with many electric appliances. For adding a load to an existing home, 220.83 (120.83 in NEC 2026) has its own method.