
Wire Ampacity & Derating Calculator (NEC 310.16)
Find the real-world power limit of your wire in hot or crowded conditions.
1Conductor Specs
2Conditions
No Derating
Usually 75°C for modern breakers.
Allowable Ampacity Final AmpacityThe maximum safe current the conductor can carry after all adjustments (NEC 310.15).
Calculation Breakdown
Base Ampacity Base Table ValueStarting value from NEC Table 310.16.
12 AWG Copper @ 90C column (Table 310.16)
Temp Correction Temperature FactorCorrection factor for ambient temperatures other than 30°C (86°F).
Ambient 30°C (86°F)
Fill Adjustment Fill FactorAdjustment for more than 3 current-carrying conductors in a raceway.
3 Current-Carrying Conductors
Ampacity Adjustment Formula
NEC 310.15(B) & (C) Adjustments
NEC 310.15(B) outlines ambient temperature correction factors. NEC 310.15(C)(1) requires ampacity reduction when more than 3 current-carrying conductors are bundled together in a raceway or cable.
Frequently Asked Questions
When do I need to derate wire?
You must derate when (1) the ambient temperature exceeds 86°F (30°C) or (2) there are more than 3 current-carrying conductors in the same pipe/raceway.
Does the neutral wire count as a current-carrying conductor?
Typically, no. In a balanced system, it carries only unbalanced current. However, if the load is mostly non-linear (electronics, LED lights), the neutral DOES count.
Can I start derating from the 90°C column?
Yes! Even if your breakers are rated 75°C, you can use the 90°C ampacity of THHN/THWN-2 conductors as the starting point for derating calculations.