314.16(B)

NEC 2020 Table 314.16(B) Volume Allowance Chart

NEC 2020 • 2023 • 2026 COMPLIANT
Select NEC Edition:NEC 2020NEC 2023NEC 2026

Per-conductor cubic inch volume requirements used for calculating non-standard box fill.

Size of Conductor (AWG)Free Space per Conductor (in³)
181.50
161.75
142.00
122.25
102.50
83.00
65.00

Use this table in a calculator

Professional Usage Disclaimer

This data is provided for informational purposes only. Always verify with the latest edition of the National Electrical Code (NFPA 70) and consult with a licensed electrical professional or AHJ (Authority Having Jurisdiction) before performing any electrical work. Zing² is a reference tool, not a substitute for qualified engineering.