Transformer Sizing Calculator (kVA & Amps)

Select the ideal kVA capacity and protection for any equipment load.

1System Specs

2Load Specs

3Protection Method

-kVA
Calculated Load-
Primary Current (@ 480V)-

Primary Protection (NEC 450.3)

1

Primary Current

Based on 45 kVA Transformer

54.1 A
2

Max Rating

125% of Primary (Next Size Up)

67.7 A
Recommended Primary Breaker70 A
Voltage480 V

Popular transformer Configurations

Transformer kVA Formula

1Φ: kVA = (V × I) / 1000
3Φ: kVA = (V × I × 1.732) / 1000

NEC 450.3 Overcurrent Protection

NEC Table 450.3(B) dictates the maximum rating for primary and secondary overcurrent protection (fuses/breakers) for transformers 1000V or less. Common values are 125% for primary only, or 250% primary / 125% secondary.

Frequently Asked Questions

How do I size the breaker for a transformer?

Standard practice is to size the primary breaker at 125% of the primary full load current (FLC). If that doesn't correspond to a standard size, you may go up to the next standard size (Note 1 to Table 450.3(B)).

What is the difference between kVA and kW?

kW is real power (working power). kVA is apparent power (total power). They are related by the Power Factor (PF): kW = kVA × PF.

Why uses 1.732 for three-phase?

1.732 is the square root of 3. In three-phase power, it accounts for the phase angle difference between the three legs.

Check Out More Tools