Grounding Electrode Conductor (GEC) Calculator

Determine the correct ground wire size for any service or circuit.

What Are You Grounding?

Main Service Panel / Grounding Electrode Conductor (GEC)

Grounding Electrode Conductor (GEC)

-
Material-
Wire Color-
NEC 250.66Minimum required size for Grounding Electrode Conductor.

Main Bonding Jumper (MBJ) / SSBJ

-
NEC 250.102(C)(1)Same as GEC up to 1100 kcmil. Above 1100 kcmil: 12.5% of phase conductor area.

Interior Metal Water Piping Bond

-
NEC 250.104(A)Sized per NEC Table 250.102(C)(1). Used to bond interior metal water piping to the grounding system.

Important Notes

The GEC connects the grounding electrode to the service panel.

Per NEC 250.66, the GEC is never required to be larger than 3/0 AWG copper.

The Main Bonding Jumper (MBJ) connects the grounded conductor to the equipment grounding system at the service.

Grounding Sizing Rules

GEC is sized based on the largest ungrounded service entrance conductor (Table 250.66). EGC is sized based on the rating of the overcurrent device/breaker (Table 250.122).

NEC 250.66 & 250.122

Table 250.66 dictates the size of the Grounding Electrode Conductor (wire to ground rod/water pipe). Table 250.122 dictates the Equipment Grounding Conductor (safety ground wire with the circuit).

Frequently Asked Questions

What is the difference between GEC and EGC?

GEC (Grounding Electrode Conductor) connects the system to earth (ground rod). EGC (Equipment Grounding Conductor) connects device metal parts back to the panel to trip the breaker during a fault.

Can I use aluminum for grounding?

Yes, but it cannot be used in direct contact with masonry or earth, and usually must be larger than the equivalent copper wire.

Does the ground wire need to be larger if I increase wire size for voltage drop?

Yes. NEC 250.122(B) states that if ungrounded conductors are increased in size (e.g., for voltage drop), the EGC must be increased proportionately.

Check Out More Tools